Building Wire & Cable

Purposes Of Building Wire & Cables

Building wire & cables are mainly utilized in low voltage distribution wiring on indoor building and electric circuit wiring of instruments or equipments.

It can be classified as following types:

  • 600V PVC Insulated Wire (IV)
  • 600V PVC Insulated PVC Sheathed Cable (VV)
  • 600V PVC Insulated PVC Sheathed Control Cable (CVV)
  • 600V XLPE Insulated PVC Sheathed Cable (XLPE-PVC)

Characteristic of Building Wire & Cable

Type of Wire & Cable IV、VV&CVV XLPE-PVC
Max. Conductor Temperature Continuous Operating 60℃ 90℃
Emergency/Overload 100℃ 130℃
Short Circuit (max. 5 seconds) 150℃ 250℃
Insulation Resistance (MΩ-km, 20℃) Min.20 Min.400
Dielectric Strength (kV/mm) Min.20 Min.40
Resistance in Sulfuric Acid (30%) Good Good
Resistance in Hydrochloric Acid (10%) Good Good
Resistance in Alcohol Good Good
Resistance in Acetic Acid (5%) Good Good
Resistance In Sodium Hydroxide (10%) Good Good
Cold Resistance -10℃ -40℃
Flame Retardant (Horizontal) Self extinguished when flame removed Self extinguished when flame removed

PEWC supplied excellent quality products with CNS certificate as follows:

  • 600V PVC Insulated Wire (IV):CNS certification no. 1267
  • 600V PVC Insulated PVC Sheathed Cable (VV):CNS certification no. 3620
  • 600V XLPE Insulated PVC Sheathed Cable (XLPE-PVC):CNS certification no. 4491

Besides of the above mentioned characteristics, PEWC can also supplied Building wire & cable complied with the “Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS)”. PEWC is pleased to welcome both old and new acquaintances to choose it.